Annotation of researchv10no/cmd/tbl/tmp/sample30, revision 1.1.1.1

1.1       root        1: .1C
                      2: .ft3
                      3: .ps 10
                      4: .vs 12
                      5: .ce 3
                      6: TABLE B
                      7: .sp 0.5
                      8: RECOMMENDED WORK ALLEY WIDTHS FOR BOTH ABOVE- AND
                      9: BELOW-SURFACE CEFs
                     10: .sp 0.5
                     11: .TS H
                     12: box expand;
                     13: cw(2.3i)p8f3 |cp8f3 |cp8f3
                     14: ^ |cp8f3 |cp8f3 .
                     15: .vs 10
                     16: .sp 1
                     17: TYPE OF ACTIVITY*      MINUMUM WIDTH   RECOMMENDED WIDTH
                     18:        (Inches)        (Inches)
                     19: _
                     20: .sp 0.5
                     21: .TH
                     22: .T&
                     23: lp10f1 |np10f1 |np10f1 .
                     24: .vs 12
                     25: T{
                     26: .na
                     27: .ft2
                     28: Low activity
                     29: .ft1
                     30: (no through passage) with cable positioned on one or both sides 
                     31: of the work area.
                     32: T}     36\(dg  40\(dg
                     33: _
                     34: .sp 0.5
                     35: T{
                     36: .ft2
                     37: Low activity
                     38: .ft1
                     39: with permanently installed rolling ladder, and cable
                     40: on only one side of the alley (includes 18 inches for ladder width).
                     41: T}     54      60
                     42: _
                     43: .sp 0.5
                     44: T{
                     45: .ft2
                     46: Moderate activity
                     47: .ft1
                     48: with clearance for passage of craft person behind
                     49: seated splicer (includes 20 inches for sideway passage of
                     50: other craft persons) and cable on one or both sides of the work area.
                     51: T}     56      62
                     52: _
                     53: .sp 0.5
                     54: T{
                     55: .ft2
                     56: Heavy activity
                     57: .ft1
                     58: with clearance for passage of both outside and central
                     59: office workers behind seated splicer (includes a minimum 27 inches for
                     60: passage of other persons and/or central office work operations).
                     61: T}     63      70
                     62: .ad
                     63: .TE
                     64: .ft1
                     65: .sp 1
                     66: .in 0.4i
                     67: .IP *\0
                     68: Activity refers to the frequency of passage of other craft persons past the
                     69: splicer's work space.  (Low \(<= one per hour; moderate \(<= five per hour;
                     70: heavy \0\0 five per hour.)
                     71: .IP
                     72: .in 0
                     73: .sp 1
                     74: .in 0.4i
                     75: .IP \(dg\0
                     76: In central office buildings where the CEF is positioned such that other
                     77: building area occupants must pass through the CEF area to exit, then the
                     78: minimum distance between the equipment frame and the nearest obstruction
                     79: shall not be less than 44 inches.
                     80: .IP